Department for Communities and Local Government, (2019) Loft conversions. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 2: Means of escape - dwellinghouses, 1 (2.23). RIBA Publishing Publication, London, p. 18. ISBN 9781859469156

Full text not available from this repository.

Abstract

An alternative approach to that described in paragraph 2.21 would be to comply with all of the following.
a. Provide sprinkler protection to the open-plan areas.
b. Provide a fire resisting partition (minimum REI 30) and door (minimum E 20) to separate the ground storey from the upper storeys. The door should allow occupants of the loft room access to a first storey escape window.
c. Separate cooking facilities from the open-plan area with fire resisting construction (minimum REI 30).