Protected power circuits

Department for Communities and Local Government, (2019) Protected power circuits. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 3: Means of escape – flats, 1 (3.47). RIBA Publishing Publication, London, p. 31. ISBN 9781859469156

Full text not available from this repository.

Abstract

A protected circuit to operate equipment during a fire should achieve all of the following.
a. Cables should achieve PH 30 classification when tested in accordance with BS EN 50200 (incorporating Annex E) or an equivalent standard.
b. It should only pass through parts of the building in which the fire risk is negligible.
c. It should be separate from any circuit provided for another purpose.