Department for Communities and Local Government, (2019) Fire doorsets C1. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Appendix C: Fire doorsets, 1 (C1). RIBA Publishing Publication, London, 134 - 134. ISBN 9781859469156
Full text not available from this repository.Abstract
All fire doorsets should have the performance shown in Table C1, based on one of the following.
a. Fire resistance in terms of integrity, for a period of minutes, when tested to BS 476-22, e.g. FD 30.
A suffix (S) is added for doorsets where restricted smoke leakage at ambient temperatures is
needed.
b. As determined with reference to Commission Decision 2000/367/EC regarding the
classification of the resistance to fire performance of construction products, construction
works and parts thereof. All fire doorsets should be classified in accordance with BS EN 13501-2,
tested to the relevant European method from the following.
i. BS EN 1634-1.
ii. BS EN 1634-2.
iii. BS EN 1634-3.
c. As determined with reference to European Parliament and Council Directive 95/16/EC (which
applies to lifts that permanently serve buildings and constructions and specified safety
components) on the approximation of laws of Member States relating to lifts (‘Lifts Directive’)
implementing the
Item Type: | Book Section |
---|---|
Additional Information: | mml-maui-text-analytics-keywords |
Uncontrolled Keywords: | fire doorset, doorset, should, fire resistance, fire resisting (Fire resistance), firefighting lift |
Subjects: | Appendix C: Fire doorsets Building standards |