Fire doorsets C9

Department for Communities and Local Government, (2019) Fire doorsets C9. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Appendix C: Fire doorsets, 1 (C9). RIBA Publishing Publication, London, 135 - 135. ISBN 9781859469156

Full text not available from this repository.

Abstract

Rolling shutters should be capable of manual opening and closing for firefighting purposes (see Section 15). Rolling shutters across a means of escape should only be released by a heat sensor, such as a fusible link or electric heat detector, in the immediate vicinity of the door. Unless a shutter is also intended to partially descend as part of a boundary to a smoke reservoir, shutters across a means of escape should not be closed by smoke detectors or a fire alarm system.

Item Type: Book Section
Additional Information: mml-maui-text-analytics-keywords
Uncontrolled Keywords: link 1, fire alarm system, should, means of escape, non-self-resetting energy cut-out, automatic control
Subjects: Appendix C: Fire doorsets
Building standards
Depositing User: admin
Date Deposited: 17 Jul 2020 06:32
Last Modified: 29 Sep 2022 21:01
URI: https://buildvoc.co.uk/id/eprint/1108