Department for Communities and Local Government, (2019) Free area of smoke ventilators. In: Approved Document B: Fire Safety - Volume 1: Dwellings. Appendix D: Methods of measurement, 1 (D5). RIBA Publishing Publication, p. 144.
Full text not available from this repository.Abstract
The free area of a smoke ventilator should be measured by either of the following.
a. The declared aerodynamic free area in accordance with BS EN 12101-2.
b. The total unobstructed cross-sectional area (geometric free area), measured in the plane where
the area is at a minimum and at right angles to the direction of air flow (Diagram D7).