Department for Communities and Local Government, (2019) Water supplies and pumps. In: Approved Document B: Fire Safety - Volume 1: Dwellings. Appendix E: Sprinklers, 1 (E6). RIBA Publishing Publication, p. 146.
Full text not available from this repository.Abstract
For the systems described in paragraph E5, both of the following apply if pumps are used to draw
water from two tanks.
a. Each pump should be able to draw water from either tank.
b. Any one pump, or either tank, should be able to be isolated.
The sprinkler water supplies should not be used as connections for other services or other fixed
firefighting systems.