Department for Communities and Local Government, (2022) Provision of firefighting shafts. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2022 ed. Section 15: Access to buildings for firefighting personnel – flats, 1 (15.5). RIBA Publishing Publication, London, p. 104. ISBN 9781859469156
This is the latest version of this item.
Abstract
In buildings where a firefighting shaft is required, a minimum of two firefighting shafts should be provided in either of the following situations.
a. A building that has both of the following.
i. A storey with a floor area of 900m2 or more.
ii. A storey 18m or more above the fire and rescue service vehicle access level.
b. A building with a basement storey which is more than 900m2.