Escape from upper storeys a maximum of 4.5m above ground level

Department for Communities and Local Government, (2019) Escape from upper storeys a maximum of 4.5m above ground level. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 3: Means of escape – flats, 1 (3.16). RIBA Publishing Publication, London, p. 21. ISBN 9781859469156

Full text not available from this repository.

Abstract

All habitable rooms (excluding kitchens) should have either of the following.
a. An emergency escape window or external door, as described in paragraph 3.6.
b. In multi-storey flats, direct access to a protected internal stairway (minimum REI 30) leading to an exit from the flat.

Item Type: Book Section
Additional Information: mml-maui-text-analytics-keywords
Uncontrolled Keywords: storey exit, habitable room, habitable room, circulation space, protected stairway, leading edge (of door), direct distance, kitchen, exit passageway, following edge (of door)
Subjects: T Technology > TH Building construction > Building standards > fire safety - volume 1: dwellings. 2019 edition - for use in england > Section 3: Means of escape – flats
K Law > The Building Regulations 2010 > B1: Means of warning and escape