Department for Communities and Local Government, (2019) Flats with an alternative exit. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 3: Means of escape – flats, 1 (3.19). RIBA Publishing Publication, London, p. 23. ISBN 9781859469156

Full text not available from this repository.

Abstract

Where access from any habitable room to the entrance hall or flat entrance is impossible without passing through another room, all of the following conditions should be met (Diagram 3.4).
a. Bedrooms should be separated from living accommodation by fire resisting construction (minimum REI 30) and fire doorsets (minimum E 20).
b. The alternative exit should be in the part of the flat that contains the bedrooms.

Item Type: Book Section
Additional Information: mml-maui-text-analytics-keywords
Uncontrolled Keywords: alternative exit, fire doorset, access room, habitable room, habitable room, should, accessible entrance, high-usage entrance door
Subjects: Section 03: Means of escape – flats