Department for Communities and Local Government, (2019) Common escape routes. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 3: Means of escape – flats, 1 (3.35). RIBA Publishing Publication, London, p. 30. ISBN 9781859469156

Full text not available from this repository.

Abstract

Divide a common corridor connecting two or more storey exits with a fire doorset fitted with a self-closing device (minimum E 30 Sa). See Diagram 3.8. Associated screens should be fire resisting. Site doors so that smoke does not affect access to more than one stair.

Item Type: Book Section
Additional Information: mml-maui-text-analytics-keywords
Uncontrolled Keywords: self-closing device, fire doorset, doorset, storey exit, associate, should, radial gangway