Department for Communities and Local Government, (2019) Junction of compartment wall with roof. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 5: Internal fire spread – dwellinghouses, 1 (5.15). RIBA Publishing Publication, London, p. 52. ISBN 9781859469156
Full text not available from this repository.Abstract
As an alternative to the provisions of paragraphs 5.12 to 5.14, the compartment wall may extend through the roof for a minimum of either of the following (see Diagram 5.2c).
a. Where the height difference between the two roofs is less than 375mm, 375mm above the top surface of the adjoining roof covering.
b. 200mm above the top surface of the adjoining roof covering where either of the following applies.
i. The height difference between the two roofs is 375mm or more.
ii. The roof coverings either side of the wall are of a material classified as BROOF(t4).