Department for Communities and Local Government, (2019) Construction and fixings for cavity barriers. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 5: Internal fire spread – dwellinghouses, 1 (5.20). RIBA Publishing Publication, London, p. 55. ISBN 9781859469156
Full text not available from this repository.
Official URL: https://www.gov.uk/government/publications/fire-sa...
Abstract
Cavity barriers, tested from each side separately, should provide a minimum of both of the following:
a. 30 minutes’ integrity (E 30)
b. 15 minutes’ insulation (I 15).
They may be formed by a construction provided for another purpose if it achieves the same performance.