Department for Communities and Local Government, (2019) Construction and fixings for cavity barriers. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 5: Internal fire spread – dwellinghouses, 1 (5.23). RIBA Publishing Publication, London, p. 55. ISBN 9781859469156
Full text not available from this repository.Abstract
Cavity barriers should be fixed so their performance is unlikely to be made ineffective by any of the following.
a. Movement of the building due to subsidence, shrinkage or temperature change, and movement of the external envelope due to wind.
b. During a fire, collapse of services penetrating the cavity barriers, either by the failure of the supporting system or through degradation of the service itself (e.g. by melting or burning).
c. During a fire, failure of the cavity barrier fixings. (In roof spaces, where cavity barriers are fixed to roof members, there is no expectation of fire resistance from roof members provided for the purpose of support.)
d. During a fire, failure of any material or construction to which cavity barriers abut. (For example, a suspended ceiling that continues over a fire resisting wall or partition collapses, and the cavity barrier fails prematurely because the ceiling was not designed to provide a minimum fire resistance of EI 30.)
Item Type: | Book Section |
---|---|
Additional Information: | mml-maui-text-analytics-keywords |
Uncontrolled Keywords: | cavity barrier, barrier, cavity, suspended ceiling, accessible threshold |
Subjects: | Section 05: Internal fire spread – dwellinghouses B3: Internal fire spread (structure) Building standards |
Date Deposited: | 15 Feb 2020 06:07 |
Last Modified: | 29 Sep 2022 21:01 |
URI: | https://buildvoc.co.uk/id/eprint/499 |