Department for Communities and Local Government, (2019) Junction of compartment wall with roof. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 7: Compartmentation/sprinklers – flats, 1 (7.18). RIBA Publishing Publication, London, p. 61. ISBN 9781859469156
Full text not available from this repository.Abstract
As an alternative to the provisions of paragraph 7.16 or 7.17, the compartment wall may extend through the roof for a minimum of either of the following (see Diagram 5.2c).
a. Where the height difference between the two roofs is less than 375mm, 375mm above the top surface of the adjoining roof covering.
b. 200mm above the top surface of the adjoining roof covering where either of the following applies.
i. The height difference between the two roofs is 375mm or more.
ii. The roof coverings either side of the wall are of a material classified as BROOF(t4).
Item Type: | Book Section |
---|---|
Additional Information: | mml-maui-text-analytics-keywords |
Uncontrolled Keywords: | height, roof, wall, compartment wall |
Subjects: | Section 07: Compartmentation/sprinklers – flats B3: Internal fire spread (structure) Building standards |
Date Deposited: | 15 Feb 2020 05:59 |
Last Modified: | 29 Sep 2022 21:02 |
URI: | https://buildvoc.co.uk/id/eprint/557 |