Department for Communities and Local Government, (2019) Protected escape routes. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 8: Cavities – flats, 1 (8.5). RIBA Publishing Publication, London, p. 65. ISBN 9781859469156
Full text not available from this repository.Abstract
If the fire resisting construction of a protected escape route is either of the following.
a. Not carried to full storey height.
b. At the top storey, not carried to the underside of the roof covering.
Then the cavity above or below the fire resisting construction should be either of the following.
i. Fitted with cavity barriers on the line of the enclosure.
ii. For cavities above the fire resisting construction, enclosed on the lower side by a fire resisting ceiling (minimum EI 30) that extends throughout the building, compartment or separated part (see Diagram 8.3).