Department for Communities and Local Government, (2019) Double-skinned corrugated or profiled roof sheeting. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 8: Cavities – flats, 1 (8.7). RIBA Publishing Publication, London, p. 67. ISBN 9781859469156
Full text not available from this repository.Abstract
Cavity barriers are not required between double-skinned corrugated or profiled insulated roof sheeting, if the sheeting complies with all of the following.
a. The sheeting is rated class A2-s3, d2 or better.
b. Both surfaces of the insulating layer are rated class C-s3, d2 or better.
c. Both surfaces of the insulating layer make contact with the inner and outer skins of cladding (Diagram 8.4).