Department for Communities and Local Government, (2019) Construction and fixings for cavity barriers. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 8: Cavities – flats, 1 (8.8). RIBA Publishing Publication, London, p. 68. ISBN 9781859469156
Full text not available from this repository.
Official URL: https://www.gov.uk/government/publications/fire-sa...
Abstract
Cavity barriers, tested from each side separately, should provide a minimum of both of the following:
a. 30 minutes’ integrity (E 30)
b. 15 minutes’ insulation (I 15).
They may be formed by a construction provided for another purpose if it achieves the same performance.
Item Type: | Book Section |
---|---|
Additional Information: | mml-maui-text-analytics-keywords |
Uncontrolled Keywords: | cavity barrier, barrier, cavity |
Subjects: | Section 08: Cavities – flats B3: Internal fire spread (structure) Building standards |
Date Deposited: | 15 Feb 2020 05:52 |
Last Modified: | 29 Sep 2022 21:01 |
URI: | https://buildvoc.co.uk/id/eprint/618 |