Department for Communities and Local Government, (2019) Alternative supply of water. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 14: Fire mains and hydrants – flats, 1 (14.13). RIBA Publishing Publication, London, p. 100. ISBN 9781859469156
![[img]](https://www.buildvoc.co.uk/style/images/fileicons/text.png)
797.json
Download (2kB)
Abstract
The alternative source of water supply should be one of the following, subject to consultation with the local fire and rescue service.
a. A charged static water tank with a minimum capacity of 45,000 litres.
b. A spring, river, canal or pond that is capable of fulfilling both of the following conditions.
i. Providing or storing a minimum of 45,000 litres of water at all times.
ii. Providing access, space and a hardstanding for a pumping appliance.
c. Any other water supply that the local fire and rescue service considers appropriate.