Provision of firefighting shafts

Department for Communities and Local Government, (2019) Provision of firefighting shafts. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 15: Access to buildings for firefighting personnel – flats, 1 (15.3). RIBA Publishing Publication, London, p. 104. ISBN 9781859469156

Full text not available from this repository.

Abstract

A building with basement storeys should have firefighting shafts in accordance with the following.
a. There is a basement more than 10m below the fire and rescue service vehicle access level. The firefighting shafts should contain firefighting lifts.
b. There are two or more basement storeys, each with a minimum area of 900m2. The firefighting shafts do not need to include firefighting lifts.
The building’s height and size determine whether firefighting shafts also serve upper storeys.

Item Type: Book Section
Additional Information: mml-maui-text-analytics-keywords
Uncontrolled Keywords: firefighting shaft, basement storey, firefighting lift, basement, firefighting lift, storey, building, should, building
Subjects: Section 15: Access to buildings for firefighting personnel – flats
B5: Access and facilities for the fire service
Building standards
Date Deposited: 28 Feb 2020 21:03
Last Modified: 29 Sep 2022 21:02
URI: https://buildvoc.co.uk/id/eprint/803

Actions (login required)

View Item
View Item