Department for Communities and Local Government, (2019) Provision of firefighting shafts. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 15: Access to buildings for firefighting personnel – flats, 1 (15.7). RIBA Publishing Publication, London, p. 104. ISBN 9781859469156
Full text not available from this repository.Abstract
In any building, the hose laying distance should meet all of the following conditions.
a. A maximum of 60m from the fire main outlet in a firefighting shaft (see Diagram 15.3).
b. Additionally, where sprinklers have not been provided in accordance with Appendix E, the hose laying distance should be a maximum of 45m from a fire main outlet in a protected stairway (although this does not imply that the protected stairway needs to be designed as a firefighting shaft (see Diagram 15.3)).