Provision of firefighting shafts

Department for Communities and Local Government, (2019) Provision of firefighting shafts. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 15: Access to buildings for firefighting personnel – flats, 1 (15.7). RIBA Publishing Publication, London, p. 104. ISBN 9781859469156

Full text not available from this repository.

Abstract

In any building, the hose laying distance should meet all of the following conditions.
a. A maximum of 60m from the fire main outlet in a firefighting shaft (see Diagram 15.3).
b. Additionally, where sprinklers have not been provided in accordance with Appendix E, the hose laying distance should be a maximum of 45m from a fire main outlet in a protected stairway (although this does not imply that the protected stairway needs to be designed as a firefighting shaft (see Diagram 15.3)).

Item Type: Book Section
Additional Information: mml-maui-text-analytics-keywords
Uncontrolled Keywords: firefighting shaft, should, fire protection
Subjects: Section 15: Access to buildings for firefighting personnel – flats
B5: Access and facilities for the fire service
Building standards