Department for Communities and Local Government, (2019) Provision of smoke outlets. In: Approved Document B: Fire Safety - Volume 1: Dwellings. 2019 ed. Section 16: Venting of heat and smoke from basements – flats, 1 (16.3). RIBA Publishing Publication, London, p. 106. ISBN 9781859469156
Text
830.json
Download (1kB)
830.json
Download (1kB)
Official URL: https://www.gov.uk/government/publications/fire-sa...
Abstract
Smoke outlets connecting directly to the open air should be provided from every basement storey, except for any basement storey that has both of the following.
a. A maximum floor area of 200m2.
b. A floor a maximum of 3m below the adjacent ground level.
Item Type: | Book Section |
---|---|
Additional Information: | mml-maui-text-analytics-keywords |
Uncontrolled Keywords: | basement storey, basement, final exit |
Subjects: | Section 16: Venting of heat and smoke from basements – flats B5: Access and facilities for the fire service Building standards |