Department for Communities and Local Government, (2019) Table 9.1 Maximum nominal internal diameter of pipes passing through a compartment wall/floor. [Image]
Preview |
b-volume-1-table-9-1-maximum-nominal-internal-diameter-of-pipes-passing-through-a-compartment-wall-floor.jpg
Download (431kB) | Preview
Image
b-volume-1-table-9-1-maximum-nominal-internal-diameter-of-pipes-passing-through-a-compartment-wall-floor.svg
Download (36kB)
b-volume-1-table-9-1-maximum-nominal-internal-diameter-of-pipes-passing-through-a-compartment-wall-floor.svg
Download (36kB)
Text
b-volume-1-table-9-1-maximum-nominal-internal-diameter-of-pipes-passing-through-a-compartment-wall-floor.docx
Restricted to Repository staff only
Download (10kB)
b-volume-1-table-9-1-maximum-nominal-internal-diameter-of-pipes-passing-through-a-compartment-wall-floor.docx
Restricted to Repository staff only
Download (10kB)
Text
888.json
Download (2kB)
888.json
Download (2kB)
Official URL: https://www.gov.uk/government/publications/fire-sa...
Abstract
NOTES:
1. Any metal (such as cast iron, copper or steel) which, if exposed to a temperature of 800°C, will not soften or fracture to the extent that flame or hot gas will pass through the wall of the pipe.
2. uPVC pipes that comply with either BS 4514 or BS 5255.
3. These diameters are only in relation to pipes that form part of an above-ground drainage system and are enclosed as shown in Diagram 9.1. In other cases, the maximum diameters given for situation 5 apply.
Item Type: | Image |
---|---|
Additional Information: | mml-maui-text-analytics-keywords |
Uncontrolled Keywords: | pipe, factory-made metal chimneys (also known as system chimneys), non-self-resetting energy cut-out |
Subjects: | B3: Internal fire spread (structure) Section 09: Protection of openings and fire‑stopping Building standards |
Depositing User: | Umesh Pardale |
Date Deposited: | 11 May 2020 05:51 |
Last Modified: | 29 Sep 2022 21:03 |
URI: | https://buildvoc.co.uk/id/eprint/888 |