Diagram 5.1 Separation between garage and dwellinghouse

Department for Communities and Local Government, (2019) Diagram 5.1 Separation between garage and dwellinghouse. [Image]

[img]
Preview
Image
b-volume-1-diagram-5-1-separation-between-garage-and-dwellinghouse.jpg

Download (250kB) | Preview
[img] Image
b-volume-1-diagram-5-1-separation-between-garage-and-dwellinghouse.svg

Download (16kB)
[img] Text
b-volume-1-diagram-5-1-separation-between-garage-and-dwellinghouse.docx
Restricted to Repository staff only

Download (8kB)

Abstract

Fire doors between the garage and dwellinghouse to have a minimum fire resistance of E30 Sa and be fitted with a self-closing device
Wall and any floor between the garage and dwellinghouse to have a minimum fire resistance of REI 30 from the garage side
The door opening threshold should be a minimum of 100mm above garage floor or
Floor to fall away from door to the outside
See paras 5.6 and 5.7

Item Type: Image
Additional Information: mml-maui-text-analytics-keywords
Uncontrolled Keywords: self-closing device, dwellinghouse, fire wall, wall, should, fire resisting (Fire resistance), fire resistance, floor 02, floor 01, accessible threshold
Subjects: B3: Internal fire spread (structure)
Section 05: Internal fire spread – dwellinghouses
Building standards