Diagram 12.1 Limitations on spacing and size of plastic rooflights that have a class D-s3, d2 or TP(b) lower surface

Department for Communities and Local Government, (2019) Diagram 12.1 Limitations on spacing and size of plastic rooflights that have a class D-s3, d2 or TP(b) lower surface. [Image]

[img]
Preview
Image
B-7375~1.JPG

Download (290kB) | Preview
[img] Image
b-volume-1-diagram-12-1-limitations-on-spacing-and-size-of-plastic-rooflights-that-have-a-class-d-s3-d2.svg

Download (7kB)
[img] Text
b-volume-1-diagram-12-1-limitations-on-spacing-and-size-of-plastic-rooflights-that-have-a-class-d-s3-d2-or-tp-b-lower surface.docx
Restricted to Repository staff only

Download (9kB)
[img] Text (Plain text conversion conversion from text to text/plain)
b-volume-1-diagram-12-1-limitations-on-spacing-and-size-of-plastic-rooflights-that-have-a-class-d-s3-d2-or-tp-b-lower surface.txt
Restricted to Repository staff only

Download (650B)

Abstract

NOTES:
1.There are restrictions on the use of plastic rooflights in the guidance to requirement B2 in Section 4.
2.Surrounding roof covering to be a material of class A2-s3, d3 or better for at least 3m distance.
3.Where Diagram 5.2a or 5.2b applies, rooflights should be at least 1500mm from the compartment wall.
See paras 12.5 and 12.6

Item Type: Image
Additional Information: mml-maui-text-analytics-keywords
Uncontrolled Keywords: rooflight, unprotected area, fluepipe, should
Subjects: Section 12: Resisting fire spread over roof coverings
B4: External fire spread
Building standards